Gustav Hensel GmbH & Co. KG
ENYCASE - Cable junction boxes
Beschreibung
- Modern terminal technology
- Functional enclosure technology
- Various cable entry
Series DK
- Application: for indoor installation in industrial and commercial buildings
- With elastic membranes, which can be removed for cable entry via cable glands
- Multi-level knockouts for cable glands in different sizes
- Degree of protection: IP 66
- Material: polypropylene or polycarbonate
- Burning behaviour: glow wire test in accordance with IEC 60695-2-11: 750 °C, flame-retardant, self-extinguishing
- Colour: grey, RAL 7035
Series KF
- Application: weatherproof, for unprotected outdoor installation in harsh environment and offshore applications
- Degree of protection: IP 66 / IP 67 / IP 69
- with cable glands as accessories, temporary submersion up to 1 meter
- Weatherproof: UV-resistant, rainwater-proof, temperature-resistant, saltwater-proof
- Material: PC-GFS polycarbonate
- Burning behaviour: Glow wire test in accordance with IEC 60695-2-11: 960 °C, flame-retardant, self-extinguishing
- Colour: grey RAL 7035 or black RAL 9011
Series WP
- Application: waterproof, for encapsulation
- Degree of protecton IP 68
- submersion up to 20 meter, 168 hours
- Sealing compound fitting the product: the quantity is always matched to the product - never too much or too little material during processing.
- Inspection and subsequent installation: The lid can be removed for inspection purposes. For subsequent installations or inspections, the sealing compound can be easily removed.
- Material: PC-GFS polycarbonate
- Burning behaviour: Glow wire test in accordance with IEC 60695-2-11: 960 °C, flame-retardant, self-extinguishing
- Colour: grey RAL 7035 or black RAL 9011
Series FK
- Application: for buildings with public traffic, to guarantee the emergency power supply in the event of a fire
- Intrinsic fire resistance in accordance with DIN 4102 Part 12 (German standard) in combination with function-retaining cables
- Insulation integrity PH120 in accordance with BS EN 50200 in combination with insulation retaining cables
- Screw anchors, high-temperature-resistant ceramic terminal E30 up to E90 and cable entries included as standard
- Multi-level knockouts for cable glands in different sizes
- Material: PC-GFS polycarbonate
- Glow wire test in accordance with IEC 60695-2-11: 960 °C, flame-retardant, self-extinguishing
- Colour: orange, RAL 2003
- Cable junction box for large cable cross sections up to 50 mm²
Series KX
- Application: for use in potentially explosive atmospheres, suitable for Ex zone 2 and 22
- Ex marking for explosive gas atmospheres: II 3G Ex ec IIC T6 Gc
- Ex marking for explosive dust atmospheres: II 3D Ex tc IIIC T85 Dc
- With drill markings on the box walls for flexible positioning of the cable entries
- Degree of protection IP 66, Ex cable glands available as an accessory
- Suitable for areas with a high level of mechanical hazards
- Can be closed quickly by a quarter turn - locked position well visible
- With high-position terminal or terminal blocks + Various conductor cross sections and types
- Terminals with wire protection including for flexible conductors without ferrules
- Various terminal positions
- Material: Polycarbonate
- Burning behaviour: Glow wire test according to IEC 60695-2-11: 750°C, flame retardant, self-extinguishing
- Colour: black, similar to RAL 9011